FusionModule1000B Water-Cooled IT Solution
Commissioning Guide
Figure 4-4 Opening the automatic exhaust valves on the top of the chilled water tank
There are four valves on the top of the chilled water tank and two automatic exhaust valves
have been installed for two of them. You need to open the two automatic exhaust valves.
Step 3 Wait until no air comes out from the automatic exhaust valves on the top of the chilled water
tank, and expel air for the cooling system based on
System.
To ensure that the cooling system operates properly, you need to expel air from the cooling
system before starting it.
Step 4 After air is completely expelled, fill secondary refrigerant to the cooling system. When the
system pressure reaches 0.15 MPa, shut down the auxiliary water refill devices.
Issue 02 (2017-01-10)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
4 Preparations for Power-On Commissioning
4.5.7 Expelling Air from the Cooling