Module Layout - ABB Symphony Harmony Series Instructions Manual

Analog input module
Hide thumbs Also See for Symphony Harmony Series:
Table of Contents

Advertisement

Address Selection Switch (S1)
M O D U L E S TAT U S
U 29
S1 AD D R E SS
Figure 3-1. Module Layout
WBPEEUI240774A0
6. Verify there is sufficient logic and field power for the mod-
ules in the module mounting unit.
The ASI module must have an address to communicate with
the controller. The ASI module can have any one of 64
addresses (address 0 to 63) on the I/O expander bus. This
address identifies the ASI module to the controller and must be
the same as the address set in the controller configuration data
(FCs 215 and 216, specification S1).
Set the address with the eight position address dipswitch S1
(Fig. 3-1). The six right switch positions (three through eight) of
S1 set the six-bit address. Positions one and two must remain
closed (set to zero) for normal operation (Fig. 3-2).
LE D S
J1
J2
J3
S 1
AN A L O G IN P U T
S W IT C H
C O N F IG U R AT IO N JU M P E R
BL O C K S, J1 -J1 6
The address is set in binary format. Table
example address settings for switch S1. Refer to
the diagnostic settings. Record the I/O expander bus address
of the ASI module in the space provided.
J4
J5
J6
J7
J8
J9
J10 J11 J12 J13 J14 J15
Setup and Installation
P 1
E D G E
P 3
C O N N EC T O R S
J16
P 2
T01 063C
3-1
shows some
Section 6
for
3 - 3

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Imasi23

Table of Contents