Digital Inputs; Configuration Of Time Synchronization - ABB SAM600 Operation Manual

Process bus i/o system
Hide thumbs Also See for SAM600:
Table of Contents

Advertisement

1MRK 511 434-UEN B
2.3.7

Digital inputs

SAM600 modules have four digital input channels. These digital inputs have pre-assigned
process supervision functionality as described in
Table 5:
SAM600 module
type
SAM600-CT
SAM600-VT
SAM600-TS
The voltage level of the high potential (channel is
values (24V, 48V, 110V, 125V, 220V DC). The voltage level of the low potential (channel is
0V.
The voltage level can be set as a configuration parameter on SAM600 system level and on the
individual SAM600 modules
Tool.
The high potential is detected after exceeding 80% of the selected voltage level. The low
potential is detected after falling below 20% of the selected voltage level.
Configuration parameters
failure activation level (SAM600-VT only) can configure the polarity for the fuse failure and the
test switch indication inputs. Besides the selection of the polarity (active on high potential,
active on low potential) with which test switch and fuse failure are detected as active, the
input detection can also be disabled by selecting the parameter value
case, the SAM600 module does not report any indication irrespective of the potential detected
on its digital inputs.
The polarity can be configured on SAM600 system level and on the individual SAM600 modules
in the PCM600 Parameter Setting Tool.
If the digital inputs are not disabled, then their status can influence the quality information of
the related samples in the IEC/UCA 61850-9-2LE stream (see
2.3.8

Configuration of time synchronization

Time synchronization options
The time synchronization methods of a SAM600 system are:
Synchronization by IEEE 1588 (IEC 61850-9-3 profile)
Free-running
Synchronization by 1PPS
The sample synchronization field (SmpSync) of the generated SV streams depends on the
configured synchronization method and the current state of the system.
SAM600 Process Bus I/O System
Operation Manual
Application usage of digital input channels
Digital input 1
Test switch
activation level
Test switch
activation level
Not used
Digital inputs rated voltage in the PCM600 Parameter Setting
Test switch activation level (SAM600-CT and SAM600-VT) and Fuse
The default value for the
default value for the
© Copyright 2017 ABB. All rights reserved
Table
5.
Digital input 2
Digital input 3
Not used
Not used
Fuse failure phase
Fuse failure phase
A indication
B indication
Not used
Not used
active ) for all channels can be set to different
Test switch activation level is High potential . The
Fuse failure activation level is Low potential .
SAM600 Process Bus I/O System
GUID-4D1F7D5F-687E-4D1D-8ED8-6A16E0E97595 v1
Digital input 4
Not used
Fuse failure phase
C indication
Not used
Input disabled. In this
Section
2.3.6).
GUID-8029C0AF-FC09-4FCC-9E70-459691C025B6 v1
Section 2
off ) is
19