2.
The 110 VAC cable, the 220 VAC cable, and the 24 VDC cable should be twisted, and connected to a module
within a short distance.
3.
Do not bundle 110 VAC cable, the 220 VAC cable, the 24 VDC cable, the (high-voltage high-current) main circuit,
and the I/O signal cable together. Besides, it is recommended that the distance between adjacent cables should
be more than 100 millimeters.
4.
To prevent the surge resulting from lightning, please install a surge absorber in the way shown below.
Points for attention:
1. The surge absorber and the PLC system should be grounded separately.
2. Please select the surge absorber whose working voltage is not less than the maximum allowable input voltage.
 Connecting DC power cables
1.
AHPS15-5A is independently supplied with power by a DC power supply. Please separate the power cable of the
DC power supply from the power cables for I/O devices and other devices. If there is much noise, connect an
isolating transformer.
AC power supply
100-240 V
2.
The 110 VAC cable, the 220 VAC cable, and the 24 VDC cable should be twisted, and connected to a module
within a short distance.
3.
Do not bundle 110 VAC cable, the 220 VAC cable, the 24 VDC cable, the (high-voltage high-current) main circuit,
and the I/O signal cable together. Besides, it is recommended that the distance between adjacent cables should
be more than 100 millimeters.
4.
To prevent the surge resulting from lightning, please install a surge absorber in the way shown below.
AC power supply
100-240V
S u r g e a b s o r b e r
AC power supply
100-240V
Isolating transformer
powe r
s upply
S u rg e a b s o rb e r
Ch ap te r 2 Har dware Se tu p
AHPS05-5A
I/O equipment
DC
24 V DC
AHPS15-5A
I/O equipment
Another piec e of equipment
DC power s uppl y
I/O equipment
Another piec e of equipment
2_
2 - 7