Error code
Description
The signal received by channel 6
exceeds the range of inputs which
16#A406
can be received by the hardware.
(The ERROR LED indicator is ON.)
The signal received by channel 7
exceeds the range of inputs which
16#A407
can be received by the hardware.
(The ERROR LED indicator is ON.)
16#A600
Hardware failure
16#A601
The external voltage is abnormal.
Internal error
16#A602
The CJC is abnormal.
Internal error
16#A603
The factory correction is abnormal.
The signal received by channel 0
exceeds the range of inputs which
16#A800
can be received by the hardware.
(The ERROR LED indicator is OFF.)
The signal received by channel 1
exceeds the range of inputs which
16#A801
can be received by the hardware.
(The ERROR LED indicator is OFF.)
The signal received by channel 2
exceeds the range of inputs which
16#A802
can be received by the hardware.
(The ERROR LED indicator is OFF.)
The signal received by channel 3
exceeds the range of inputs which
16#A803
can be received by the hardware.
(The ERROR LED indicator is OFF.)
The signal received by channel 4
exceeds the range of inputs which
16#A804
can be received by the hardware.
(The ERROR LED indicator is OFF.)
The signal received by channel 5
exceeds the range of inputs which
16#A805
can be received by the hardware.
(The ERROR LED indicator is OFF.)
Ch a pt er 9 T r o u bl es h oo t in g
Corrective action
Check the module parameter in HWCONFIG.
Check whether the signal received by channel 6 exceeds
the range of inputs which can be received by the hardware.
Check the module parameter in HWCONFIG.
Check whether the signal received by channel 7 exceeds
the range of inputs which can be received by the hardware.
1. Check whether the backplane is normal.
2. Check whether the module operate normally.
Check whether the external 24 V power supply to the
module is normal.
Please contact the manufacturer.
Please contact the manufacturer.
Check the module parameter in HWCONFIG.
Check whether the signal received by channel 0 exceeds
the range of inputs which can be received by the hardware.
Check the module parameter in HWCONFIG.
Check whether the signal received by channel 1 exceeds
the range of inputs which can be received by the hardware.
Check the module parameter in HWCONFIG.
Check whether the signal received by channel 2 exceeds
the range of inputs which can be received by the hardware.
Check the module parameter in HWCONFIG.
Check whether the signal received by channel 3 exceeds
the range of inputs which can be received by the hardware.
Check the module parameter in HWCONFIG.
Check whether the signal received by channel 4 exceeds
the range of inputs which can be received by the hardware.
Check the module parameter in HWCONFIG.
Check whether The signal received by channel 5 exceeds
the range of inputs which can be received by the hardware.
9_