Omron C200HX Operation Manual page 82

Hide thumbs Also See for C200HX:
Table of Contents

Advertisement

DM (Data Memory) Area
Word(s)
Bit(s)
DM 6648
00 to 07
Node number (Host Link)
00 to 31 (BCD)
08 to 11
Start code enable (RS-232C)
0: Disable; 1: Set
12 to 15
End code enable (RS-232C)
0: Disable (number of bytes received)
1: Set (specified end code)
2: CR, LF
DM 6649
00 to 07
Start code (RS-232C)
00 to FF (binary)
08 to 15
12 to 15 of DM 6648 set to 0:
Number of bytes received
00: Default setting (256 bytes)
01 to FF: 1 to 255 bytes
12 to 15 of DM 6648 set to 1:
End code (RS-232C)
00 to FF (binary)
Peripheral Port Settings (DM 6650 to DM 6654)
The following settings are accessed continually while the PC is ON.
Note To use the peripheral port set to Host Link mode after using it in peripheral bus mode, turn OFF the power once and
turn ON again or disconnect and reconnect the cable.
DM 6650
00 to 03
Port settings
0: Standard (Host Link or peripheral bus serial communications mode, 1
start bit, 7-bit data, even parity, 2 stop bits, 9,600 bps)
1: Settings in DM 6651
04 to 11
Reserved
12 to 15
Serial communications mode
0: Host Link; 1: No-protocol
DM 6651
00 to 07
Baud rate
00: 1.2K, 01: 2.4K, 02: 4.8K, 03: 9.6K, 04: 19.2K
08 to 15
Frame format
00:
01:
02:
03:
04:
05:
06:
07:
08:
09:
10:
11:
DM 6652
00 to 15
Transmission delay (Host Link)
0000 to 9999: in 10-ms units.
DM 6653
00 to 07
Node number (Host Link)
00 to 31 (BCD)
08 to 11
Start code enable (RS-232C)
0: Disable; 1: Set
12 to 15
End code enable (RS-232C)
0: Disable (number of bytes received)
1: Set (specified end code)
2: CR, LF
64
Function
Start
Length
1 bit
7 bits
1 bit
7 bits
1 bit
7 bits
1 bit
7 bits
1 bit
7 bits
1 bit
7 bits
1 bit
8 bits
1 bit
8 bits
1 bit
8 bits
1 bit
8 bits
1 bit
8 bits
1 bit
8 bits
Stop
Parity
1 bit
Even
1 bit
Odd
1 bit
None
2 bit
Even
2 bit
Odd
2 bit
None
1 bit
Even
1 bit
Odd
1 bit
None
2 bit
Even
2 bit
Odd
2 bit
None
Section 3-6
Default
0
Disabled
Disabled
Not used
(0000)
(0000)
Standard
---
Host Link
1.2 K
1 start bit, 7-bit
data, 1 stop bit,
even parity
0 ms
0
Disable
Disable

Advertisement

Table of Contents
loading

This manual is also suitable for:

C200hgC200he

Table of Contents