Special Math Instructions
Performance Specifications
Item
PID calculation method
Number of PID control loops
Sampling period
PID constants Proportional band
Integral constant
Derivative constant
Set value
Measured value
Operation output amount
Note
1. The actual integral and derivative times are calculated using the values set
in C+2 and C+3 and the time unit set in C+6.
2. Setting the 2-PID parameter (α) to 000 yields 0.65, the normal value.
3. The only CQM1 model that can use PID(––) is the CQM1-CPU4j-EV1.
---
Target value filter-type, two degrees of freedom (forward/reverse
operation)
---
No limit (1 loop per instruction)
t
0.01 to 102.3 s (See note.)
P
0.1 to 999.9%
Tik
1 to 8191, 9999 (No integral operation for sampling period multiple or
9999.)
Tdk
0 to 8191 (No derivative operation for sampling period multiple.)
SV
0 to 65,535 (Valid up to the maximum value of the input range.)
PV
0 to 65,535 (Valid up to the maximum value of the input range.)
MV
0 to 65,535 (Valid up to the maximum value of the output range.)
Note For the C200HS and the CQM1-CPU4j-EV1, the sampling period is 0.1 to
102.3 s.
Specifications
Section 5-21
267