Omron C200HX Operation Manual page 179

Hide thumbs Also See for C200HX:
Table of Contents

Advertisement

Timer and Counter Instructions
00000
TIM 000
00001
TIM 001
Example 2:
Extended Timers
00000
TIM 001
TIM 002
Example 3:
ON/OFF Delays
ON. When the SV in 005 has expired, 00201 is turned OFF. This bit will also be
turned OFF when TIM 001 is reset, regardless of whether or not SV has expired.
TIM 000
TIM 001
There are two ways to achieve timers that operate for longer than 999.9 se-
conds. One method is to program consecutive timers, with the Completion Flag
of each timer used to activate the next timer. A simple example with two
900.0-second (15-minute) timers combined to functionally form a 30-minute tim-
er.
TIM 001
TIM 002
In this example, 00200 will be turned ON 30 minutes after 00000 goes ON.
TIM can also be combined with CNT or CNT can be used to count SR area clock
pulse bits to produce longer timers. An example is provided in 5-14-4 COUNTER
– CNT.
TIM can be combined with KEEP(11) to delay turning a bit ON and OFF in refer-
ence to a desired execution condition. KEEP(11) is described in 5-9-4 KEEP –
KEEP(11).
To create delays, the Completion Flags for two TIM are used to determine the
execution conditions for setting and reset the bit designated for KEEP(11). The
bit whose manipulation is to be delayed is used in KEEP(11). Turning ON and
OFF the bit designated for KEEP(11) is thus delayed by the SV for the two TIM.
The two SV could naturally be the same if desired.
In the following example, 00500 would be turned ON 5.0 seconds after 00000
goes ON and then turned OFF 3.0 seconds after 00000 goes OFF. It is neces-
sary to use both 00500 and 00000 to determine the execution condition for TIM
Address Instruction
00000
#0150
015.0 s
00001
00200
00002
00003
00004
IR 005
00005
IR 005
00006
00201
00007
Address Instruction
00000
LD
#9000
900.0 s
00001
TIM
00002
LD
#9000
900.0 s
00003
TIM
00200
00004
LD
00005
OUT
Section 5-14
Operands
LD
00000
TIM
000
#
0150
LD
TIM
000
OUT
00200
LD
00001
TIM
001
005
AND NOT
TIM
001
OUT
00200
Operands
00000
001
#
9000
TIM
001
002
#
9000
TIM
002
00200
161