Omron C200HX Operation Manual page 344

Hide thumbs Also See for C200HX:
Table of Contents

Advertisement

Network Instructions
Controller Link Systems
Destination node: C200HX/HG/HE PC
Area
IR (Internal Relay)
LR (Link Relay)
HR (Holding Relay)
AR (Auxiliary Relay)
TC (Timer/Counter)
DM (Data Memory)
EM (Expansion DM)
326
C-series PCs
Designation
Area
IR area
00
LR area
06
HR area
07
SR area
08
Timer area (PV) 03
DM area
05
CV-series PCs have a larger area than C200HX/HG/HE PCs, so the beginning
words for sending and receiving at destination nodes cannot always be directly
specified by means of SEND(192) and RECV(193) operands. Moreover, de-
pending on circumstances, it may be desirable to change the beginning word at
destination nodes.
In such cases, set the "Direct/Indirect" control data designation to "1" (Indirect),
and specify the beginning words for sending as described below.
The beginning receive word is determined by the contents of the destination
node's D and D+1 words.
@SEND(90)
S
D
C
Note Specify the area code according to the following table.
Code
00
06
07
08
03
05
Banks 0 to 7
10 to 17
Banks 8 to 15
28 to 2F
Current bank
18
Area
Word
code
number
0 to 511
0 to 63
0 to 99
0 to 27
0 to 511
0 to 6655
S: Source node beginning send word
D: Destination node beginning receive word
C: Source node first control data word
15 14 13 12 11109 8 7 6 5 4 3 2 1 0
Area code*
0 0 0 0
D
D+1
Word address (3rd digit)
Word address (4th digit)
Destination node: CV-series PC
Area
CIO
CPU Bus Link
Auxiliary
Timer
Counter
DM (Data Memory)
EM (Expansion DM)
Section 5-26
Word address (5th digit)
Word address (1st digit)
Word address (2nd digit)
00
01
02
03
04
05
Banks 0 to 7
10 to 17
Current bank
18
Code