Expansion TERMINAL Mode The Programming Console can be put into Expansion TERMINAL mode by turn-
With keyboard mapping, bits 00 to 15 of AR 22 will be turned ON when keys 0 to
F are pressed on the Programming Console's keyboard. A bit will remain ON
after the Programming Console's key is released.
All bits in AR 22 will be turned OFF when AR 0708 is turned ON. Keyboard map-
ping inputs are disabled when AR 0708 is ON.
In addition to the keyboard mapping function, TERMINAL mode allows mes-
sages output by MSG(46) and LMSG(47) to be displayed on the Programming
Console. These messages will be erased if the Programming Console is switch
back to CONSOLE mode.
ing ON AR 0709. Pin 6 of the CPU Unit's DIP switch must be ON.
Turn off AR 0709 or pin 6 of the CPU Unit's DIP switch to return to CONSOLE
mode.
When the Programming Console is in TERMINAL mode it can perform expan-
sion keyboard mapping and display messages output by MSG(46) or
LMSG(47). With expansion keyboard mapping, bits SR 27700 through
SR 27909 will be turned ON when the corresponding key is pressed on the Pro-
gramming Console's keyboard. A bit will remain ON after the Programming Con-
sole's key is released.
All bits from SR 27700 through SR 27909 will be turned OFF when AR 0708 is
turned ON. Expansion keyboard mapping inputs are disabled when AR 0708 is
ON.
In addition to the keyboard mapping function, expansion TERMINAL mode al-
lows messages output by MSG(46) and LMSG(47) to be displayed on the Pro-
gramming Console. These messages will be erased if the Programming Con-
sole is switch back to CONSOLE mode.
The following diagram shows the correspondence between the position of Pro-
gramming Console keys and bits in the SR Area. Each key corresponds 1 to 1
with a bit. Shifted inputs are not recognized. Keys 0 to 15 correspond to bits
SR 27700 to SR 27715, keys 16 to 31 correspond to bits SR 27800 to SR 27815,
and keys 32 to 41 correspond to bits SR 27900 to SR 27909.
0
1
FUN key
6
7
12
13
18
19
24
25
30
31
36
37
The following table shows the correspondence between the actual Program-
ming Console keys and bits SR 27700 to SR 27909.
SR word
Bit
277
00
01
02
2
3
4
5
8
9
10
11
14
15
16
17
20
21
22
23
26
27
28
29
32
33
34
35
38
39
40
41
Corresponding key(s)
Section 7-2