10-3-24 STATUS WRITE –– SC
Command Format
Response Format
PC Settings
Execution Conditions
End Codes
Changes the PC operating mode.
1
x 10
x 10
@
Node no.
1
@
x 10
x 10
Node no.
"Mode data" consists of two digits (one byte) hexadecimal. With the leftmost two
bits, specify the PC operating mode. Set all of the remaining bits to "0."
1
x 16
Bit
7
6
5
4
3
0
0
0
0
0
PC Mode
RUN
MONITOR
OK
OK
Commands
Single
OK
An end code of 14 (format error) will be returned if the length of the command is
incorrect.
End code
00
Normal completion
13
FCS error
14
Format error
15
Entry number data error
18
Frame length error
19
Not executable
0
1
0
x 16
x 16
S
C
Header
Mode data
code
0
1
0
S
C
x 16
x 16
Header
End code
code
0
x 16
2
1
0
0
Bit
Operation mode
1
0
0
0
PROGRAM mode
MONITOR mode
1
0
RUN mode
1
1
PROGRAM
Write-protected
OK
OK
Multiple
Single
---
OK
Contents
Section 10-3

FCS
Terminator

FCS
Terminator
This area is different
from that of STATUS
READ.
UM Area
Read-protected
OK