Host Link Commands
Response Format
Limitations
PC Settings
Execution Conditions
End Codes
10-3-11 HR AREA WRITE –– WH
Command Format
1
0
x 10
x 10
@
W
Node no.
Header
code
Response Format
1
x 10
@
Node no.
Except for the first word of the write data, the write data can be divided into multi-
ple frames.
PC Mode
RUN
MONITOR
---
OK
Commands
Single
OK
An end code of 14 (format error) will be returned if the length of the command is
incorrect or the first word of write data isn't in the first frame.
An end code of 15 (entry number data error) will be returned if the specified write
data exceeds the data area boundary, the beginning word isn't specified in BCD,
or the write data isn't hexadecimal. (An end code of A5 will be returned instead of
15 for non-hexadecimal write data in multiple command frames.)
End code
00
Normal completion
01
Not executable in RUN mode
13
FCS error
14
Format error
15
Entry number data error
18
Frame length error
A3
Aborted due to FCS error in transmit data
A4
Aborted due to format error in transmit data
A5
Aborted due to entry number data error in transmit data
A8
Aborted due to frame length error in transmit data
Writes data to the HR area, starting from the specified word. Writing is done word
by word.
3
2
1
0
x 10
x 10
x 10
x 10
x 16
H
Beginning word
(0000 to 0099)
1
x 10
@
Node no.
0
1
0
x 10
x 16
x 16
W
L
Header
End code
code
PROGRAM
Write-protected
OK
Multiple
OK
Contents
3
2
1
0
x 16
x 16
x 16
Write data (1 word)
Write data
(for no. of words to write)
0
1
0
x 10
x 16
x 16
W
H
Header
End code
code
Section 10-3

FCS
Terminator
UM Area
Read-protected
OK
OK
Responses
Single
Multiple
OK
---

FCS
Terminator

FCS
Terminator