Omron C200HX Operation Manual page 403

Hide thumbs Also See for C200HX:
Table of Contents

Advertisement

I/O Response Time
PC Link Conditions
Minimum Response Time
Cycle time
PC with
Unit 0
Buffer in Unit 0
PC Link Unit trans-
missions
Buffer in Unit 7
PC with
Unit 7
Input
Output
In looking at the following timing charts, it is important to remember the se-
quence processing occurs during the PC scan, particular that inputs will not pro-
duce programmed-actions until the program has been execution.
PC Link Unit
Unit 0
PC
Input
Input
Note Noise may increase I/O delays.
The PC Link System used in this example consists of the following:
• No. of PCs linked:
• No. of LR points linked: 128 per PC
• Maximum PC:
• LR points used:
The following illustrates the data flow that will produce the minimum response
time, i.e., the time that results when all signals and data transmissions are pro-
cessed as soon as they occur.
Program executed.
Minimum transmission time
The equation for minimum I/O response time is thus as follows:
Response time = Input ON delay + Cycle time of PC of Unit 0 + Minimum trans-
mission time + (Cycle time of PC of Unit 7 × 2) + Output ON
delay
Inserting the following values into this equation produces a minimum I/O re-
sponse time of 149.3 ms.
Input ON delay:
Output on PC
Input on PC
LR
of Unit 7
of Unit 0
bit
LR XXXX
8
8
1,024
I/O refresh
1.5 ms
Section 6-4
PC Link Unit
Unit 7
PC
X
Output
X
LR XXXX
Output
X
I/O refresh
Program
executed.
Cycle time
385