Data Comparison
00000
25507
00200
25507
00201
25507
TIM 010
Address
00000
00001
00002
00003
00004
00005
00006
The branching structure of this diagram is important in order to ensure that
00200, 00201, and 00202 are controlled properly as the timer counts down. Be-
cause all of the comparisons here use to the timer's PV as reference, the other
operand for each CMP(20) must be in 4-digit BCD.
Instruction
Operands
LD
00000
TIM
010
#
5000
CMP(20)
TIM
010
#
4000
AND
25507
OUT
00200
LD
00200
CMP(20)
TIM
010
#
3000
TIM 010
#5000
500.0 s
CMP(20)
TIM 010
#4000
00200
Output at 100 s.
CMP(20)
TIM 010
#3000
00201
Output at 200 s.
CMP(20)
TIM 010
#2000
Output at 300 s.
00202
00204
Output at 500 s.
Address
Instruction
Operands
00007
AND
00008
OUT
00009
LD
00010
CMP(20)
TIM
#
00011
AND
00012
OUT
00013
LD
TIM
00014
OUT
Section 5-17
25507
00201
00201
010
2000
25507
00202
010
00204