CPU Unit DIP Switch

2-5
CPU Unit DIP Switch
Pin
Item
1
Memory protect
y p
2
Automatic transfer of Memory
Casse e co e s
Cassette contents
3
Message language
4
Expansion instruction setting
5
Communications parameters
6
Expansion TERMINAL mode
p
setting when AR 0712 is ON
i
h
AR 0712 i ON
20
The 6 pins on the DIP switch control 6 of the CPU Unit's operating parameters.
Setting
ON
The UM area
OFF
The UM area
ON
The contents of the Memory Cassette will be automatically
transferred to the internal RAM at start-up.
OFF
The contents will not be automatically transferred.
ON
Programming Console messages will be displayed in English.
(see note 1)
OFF
Programming Console messages will be displayed in Japanese.
ON
Expansion instructions will be set by user. Normally ON when using a
host computer for programming/monitoring.
OFF
Expansion instructions will be set to defaults.
ON
Standard communications parameters (see note 2) will be set for the
following serial communications ports.
• Built-in RS-232C port
• Peripheral port (only when a CQM1-CIF01/-CIF02 Cable is con-
nected. Does not apply to Programming Console.)
Note
OFF
The communications parameters for the following serial
communications ports will be set in PC Setup as follows:
• Built-in RS-232C port: DM 6645 and DM 6646
• Peripheral port: DM 6650 and DM 6651
Note When the CX-Programmer is connected to the peripheral port
ON
Expansion TERMINAL mode (Programming Console); AR 0712 ON.
OFF
Normal mode (Programming Console); AR 0712: OFF
Note
1. Pin 3 is set to ON when the PC is shipped.
2. The UM area contains the ladder program, fixed DM (including the PC Set-
up), expansion DM, I/O comments, the I/O table, and the UM area allocation
information.
Function
1
cannot be overwritten from a Peripheral Device.
1
can be overwritten from a Peripheral Device.
1. Standard communications parameters are as follows:
Serial communications mode: Host Link or peripheral bus;
start bits: 1; data length: 7 bits; parity: even; stop bits: 2;
baud rate: 9,600 bps
2. The CX-Programmer running on a personal computer can
be connected to the peripheral port via the peripheral bus
using the above standard communications parameters.
with the peripheral bus, either set bits 00 to 03 of DM 6650 in the
Fixed DM Area to 0 Hex (for standard parameters), or set bits 12
to 15 of DM 6650 to 0 Hex and bits 00 to 03 of DM 6650 to 1 Hex
(for Host Link or peripheral bus ) separately.