Omron C200HX Operation Manual page 486

Hide thumbs Also See for C200HX:
Table of Contents

Advertisement

Host Link Commands
10-3-7 AR AREA READ –– RJ
Command Format
1
x 10
x 10
@
Node no.
Response Format
1
x 10
x 10
@
Node no.
Limitations
PC Settings
Execution Conditions
End Codes
10-3-8 EM AREA READ –– RE
Command Format
1
0
x 10
x 10
@
R
Node no.
Header
code
468
Reads the contents of the specified number of AR words, starting from the speci-
fied word.
0
3
2
x 10
x 10
x 10
R
J
Header
Beginning word
code
(0000 to 0027)
0
1
0
x 16
x 16
x 16
R
J
Header
End code
code
The text portion of the response's first frame can contain up to 30 words.
PC Mode
RUN
MONITOR
OK
Commands
Single
OK
An end code of 14 (format error) will be returned if the length of the command is
incorrect and an end code of 15 (entry number data error) will be returned if the
specified words exceed the data area boundaries or aren't specified in BCD.
End code
00
Normal completion
13
FCS error
14
Format error
15
Entry number data error
18
Frame length error
Reads the contents of the specified number of EM words, starting from the spe-
cified word in the specified EM bank.
3
x 10
x 10
E
Bank No.
Bank no.
Beginning word
(See note.)
(0000 to 6143)
Note Input 00, 01, or 02 to specify bank number 0, 1, or 2. Input two spaces to specify
the current bank.
1
0
3
2
1
x 10
x 10
x 10
x 10
x 10
No. of words
(0001 to 0028)
3
2
1
0
x 16
x 16
x 16
Read data (1 word )
Read data
(for number of words read)
PROGRAM
Write-protected
OK
OK
Multiple
---
Contents
2
1
0
3
2
x 10
x 10
x 10
x 10
x 10
No. of words
(0001 to 6144)
Section 10-3
0

FCS
Terminator

FCS
Terminator
UM Area
Read-protected
OK
OK
Responses
Single
Multiple
OK
---
1
0

x 10
FCS
Terminator

Advertisement

Table of Contents
loading

This manual is also suitable for:

C200hgC200he

Table of Contents