3.4.2 Connection Examples of Sequence Input Circuits to SERVOPACK

CN1 connector terminals 6 to 13 are explained below.
The sequence input circuit interface connects through a relay or open-collector transistor circuit. Select a low-
current relay otherwise a faulty contact will result.
24 VDC
Note: The 24 VDC external power supply capacity must be 50 mA minimum.
Use the sink circuit for the input circuit to the SERVOPACK.
Relay Circuit Example
SERVOPACK
3.3 kΩ
+24VIN
/DEC, etc.
24 V
+
Input Signal Polarities
Signal
Level
ON
Low (L) level
OFF
High (H) level
3.4 Examples of Connection to Host Controller
Open-collector Circuit Example
24 VDC
Sink Circuit
SERVOPACK input
Voltage Level
Contact
0 V
Close
24 V
Open
SERVOPACK
+24 VIN 3.3 kΩ
/DEC, etc.
3
3-25