Removing A Ch121 V5 - Huawei FusionServer Pro CH121 V5 V100R005 Maintenance And Service Manual

Compute node
Hide thumbs Also See for FusionServer Pro CH121 V5 V100R005:
Table of Contents

Advertisement

FusionServer Pro CH121 V5 Compute Node
Maintenance and Service Guide
The following describes how to power on a compute node using the MM910 WebUI.
Procedure
Step 1 Check that the chassis is installed, the power cables are correctly connected, and the PSUs and
fan modules are in position.
Step 2 Log in to the MM910 WebUI.
For details, see
Step 3 On the HMM WebUI, choose PSUs&FANs.
The PSUs&Fans page is displayed.
Step 4 Choose PSU Management > Power Control from the navigation tree.
Figure 3-2 Power Control
Step 5 Select the compute node to be powered on, and click Power On.
The selected compute node will be powered on.
----End

3.3 Removing a CH121 V5

Procedure
Step 1 Determine the position of the compute node in the chassis.
Issue 06 (2019-08-10)
For details, see
MM910 Management Module V100R001 User
– On the MM910 CLI, run the following command:
powerstate
For details, see
MM910 Management Module V100R001 Command
12.3 Logging In to the MM910
NOTE
To power on all compute nodes at a time, select the check box in the header row and click Power On.
Copyright © Huawei Technologies Co., Ltd.
WebUI.
3 Basic Operations
Guide.
Reference.
10