Compute node
Hide thumbs Also See for FusionServer Pro CH121 V5 V100R005:
Table of Contents

Advertisement

FusionServer Pro CH121 V5 Compute Node
Maintenance and Service Guide
2.
Step 13 Install the processor and heat sink.
1.
Issue 06 (2019-08-10)
Figure 4-33 Installing the processor carrier
Place the assembled processor and heat sink upside down on the desk, and check that the
processor carrier and the heat sink are firmly secured. If the processor carrier is not
firmly buckled with the heat sink, press the processor carrier to secure it.
Figure 4-34 Checking the assembly
Remove the processor socket cover.