Epson RC90 Manual page 293

Robot controller option fieldbus i/o
Hide thumbs Also See for RC90:
Table of Contents

Advertisement

4.1.3.3 Noise Intrusion
Verify how an error occurrence condition changes while taking the following
countermeasures.
♦ Ground of FG (DRAIN) wire
Normal Grounding: Ground the DeviceNet network at only one point.
Countermeasure 1: Disconnect the wire between V- and FG.
Disconnect the wire between V- and FG when you cannot ground the FG wire.
RC700 / RC90 Option Fieldbus I/O Rev.14
Power Supply Tap
V+
CAN H
Shield (S)
CAN L
V-
V+ V- S
V+ V- FG
Communications
power supply
24 V DC
Power Supply Tap
V+
CAN H
Shield (S)
CAN L
V-
V+ V- S
V+ V- FG
Communications
Power Supply
24 V DC
V+
CAN H
Shield (S)
DeviceNet cable
CAN L
V-
Ground 100 Ω or less.
V+
CAN H
Shield (S)
DeviceNet cable
CAN L
V-
Disconnect here.
Ground 100 Ω or less.
4. Troubleshooting (DeviceNet)
281

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rc700

Table of Contents