Step 5: Basic Configuration

This section serves as an example where the AO block and TB block are configured. However,
there are a number of combinations that can be configured. This discussion is valid if the
positioner is controlled by the AO block.
1. For the Transducer block set:
ACTUATOR_3.ACT_FAIL_ACTION_1 = either 1. Valve Closed (most common) or 2. Valve
Open
ACCESSORY.REMOTE_SENSOR = 0, if remote sensor is not in use (internal Hall
sensor is used - most common)
ACTIVATE_CONTROL_SET to one of:
© 2019 Baker Hughes, a GE company, LLC. All rights reserved.
Do not deactivate the Set to OOS mode checkbox. The block must be in
OOS to change the Tag.
If the device is at the Visitor's or Temporary address range (248
(0xF8)- 251 (OxFB)), you must set the address outside of that
range.
Do not deactivate the Set to OOS mode checkbox. The block must be in
OOS to change the Address.
0: Activate Custom
Control Set (required for
Autotune as well - most
common)
3: Activate Control Set 3
6: Activate Control Set 6
(Double Acting - Slow)
1: Activate Control Set 1
(Slowest)
4: Activate Control Set 4
7: Activate Control Set 7
(Double Acting- Fast)
Masoneilan SVI FF Instruction Manual
2: Activate Control Set 2
5: Activate Control Set 5
(Fastest)