ADV SETUP Menu
Use this menu to set the pressure units, tight shutoff options and the PID setting.
Press * to select option.
Press + or - to accept and
proceed to next menu item.
Pressure Units
Menu
PSI
*
BAR
*
KPA
*
Select display
units for pressure.
© 2019 Baker Hughes, a GE company, LLC. All rights reserved.
ADV
SETUP
*
+
Pressure
Tight Shut-off
Units Menu
Low Menu
Turn tight shutoff on or off
to provide maximum actuator
force at 0%
Tight Shutoff
Menus
T.S. ON/OFF
*
<VALUE>
* - +
*
Displays tight shutoff
value if turned on.
Press * to change T.S. ON/OFF status.
Press + or - to enter new value.
Press * to accept new value and proceed
to next menu item.
Figure 58 ADV SETUP Menu
+
Tight Shut-off
+
PID Menu
High Menu
PID Menu
CSTM/AUTO
SA:SLWEST
+/-
SA:SLOW
SA:MEDIUM
SA:FAST
SA:FSTEST
#DA:SLOW
#DA:FAST
ADV
SETUP
*
+
+
Setup
*
*
*
*
*
*
Last two items for
double acting only.
*
Masoneilan SVI FF Instruction Manual
| 137
=