GE Baker Hughes Masoneilan SVI FF Installation And Operation Manual page 181

Digital positioner
Table of Contents

Advertisement

Parameter (in bold)
Sub-parameter (Index)
FAILED_STATE (74)
FF (1)
APP (2)
PROPAGATE_
APFS_TO_RB (3)
FINAL_VALUE_D (75)
STATUS (1)
VALUE (2)
FINAL_POSITION_
VALUE_D (76)
STATUS (1)
VALUE (2)
FINAL_VALUE_DINT
(77)
STATUS (1)
VALUE (2)
FINAL_POSITION_
VALUE_DINT (78)
STATUS (1)
© 2019 Baker Hughes, a GE company, LLC. All rights reserved.
Table 31 Transducer Block Parameters (Continued)
Initial
Mode
Range
Value
NA
NA
0, 1
1
MAN
OOS
BAD
0, 1
BAD
0, 1, 2,4,. .
.100
MAN
OOS
BAD
0, 1, 2,4,. .
.100
BAD
Description
Failed State status.
FF related failed State
1 - FAILED_STATE is reported by the Resource Block.
0 - No FAILED STATE condition exists.
Valve Control related Failed State:
0 - No active Valve Control Failed State condition
exists.
1 - Failed State Condition is detected in the Valve Con-
trol.
Propagate Fail State to Resource Block:
0 – Do not propagate.
1 – Propagate Failsafe state of TB to RB.
Set Point received from DO block as boolean. This point is
referred as Channel 2.
Status of the set point value.
Value:
0 - Complete close.
#0 - Complete Open.
Actual discrete valve position, provided to DO block as
boolean. This point is referred as Channel 2.
Status of the position value.
Value:
0 - Complete close.
#0 - Partially or fully open.
Set Point Received from DO block as integer. This point is
referred as Channel 3.
Status of the set point value.
Value:
0 - Complete close.
0 -100 - Discrete value of the setpoint in increments of
%.
All other values are rejected with a status - Out of Range.
Actual discrete valve position, provided to DO block as
Integer. This point is referred as Channel 3.
Status of the position value.
Masoneilan SVI FF Instruction Manual
| 181
=