Parameter (in bold)
Sub-parameter (Index)
FUNCTION (2)
DISCRETE_
SWITCH_2_CONF (83)
DIRECTION (1)
© 2019 Baker Hughes, a GE company, LLC. All rights reserved.
Table 31 Transducer Block Parameters (Continued)
Initial
Mode
Range
Value
0-13
0
MAN
OOS
MAN
OOS
MAN
OOS
Description
Custom_1_Configuration allows you to select the virtual
switch activation condition.
0. Disabled (always inactive; default).
1. Activates the switch being controlled by the DO
block.
2. Activated when position control in fault state.
3. Activated when position control is not in normal
mode.
4. Activates so the TB reports if maintenance is
required now
5. Activates so the TB reports if maintenance is
required soon.
6. Activated when the air supply is too low.
7. Activated when a Travel Deviation Alert occurs.
8. Activated when a Position HI Alert occurs.
9. Activated when a Position LO Alert occurs.
10. Always active.
11. Always Inactive (same as disabled).
12. Activated when a Reset occurred.
13. Activated when a Tight Cutoff state occurs.
Discrete switch configuration for switch 2.
Virtual switch.
Value:
1 - Normal Open (default).
0 - Normal Closed.
Masoneilan SVI FF Instruction Manual
| 183
=