GE Baker Hughes Masoneilan SVI FF Installation And Operation Manual page 98

Digital positioner
Table of Contents

Advertisement

DD Registered with FOUNDATION
Fieldbus Foundation
Diagnostics
Air Supply
Action
Supply Pressure
Air Delivery - Single Acting Relay
Air Capacity (flow coefficient)
Air Consumption
Air Supply Failure
Loss of Input Signal
Output Pressure
98 |
BHGE
Table 14 System Connectivity
Yes, available through foundation website
Options include: Valve signature, ramp, friction, stroking speed, step response,
cumulative travel, cumulative cycles, and time of operation in near-closed
position. Some diagnostics require pressure sensor and ValVue software.
Table 15 Pneumatics Single Acting Standard Flow
Dry, oil-free, 5 micron filtered and regulated air and sweet natural gas
(See ISA S7.3)
Direct Acting
20 -150 psi max. (1.4 - 10.3 bar)
Regulate 5 - 10 psi (.345 bar - .69 bar) above actuator spring range. Do
not exceed actuator rating.
10.0 scf/min (280 L/min) at 30 psi (2.1 bar) supply
16.6 scf/min (470 L/min) at 60 psi (4.2 bar) supply
23.3 scf/min (660 L/min) at 90 psi (6.3 bar) supply
Loading
Venting
0.20 scf/min (5.7 L/min) at 30 psi (2.1 bar) supply
0.28 scf/min (8 L/min) at 60 psi (4.2 bar) supply
0.42 scf/min (12 L/min) at 90 psi (6.3 bar) supply
Single Acting Relay
On supply failure the actuator output drops. Some overshoot may occur
when air pressure returns after a period without air supply pressure.
Always set control set point to 0%, and put the process control system
in manual, for smooth recovery from air supply failure.
Output drops to low pressure.
0 - 150 psi (10.3 bar) max
C
v = 0.57
C
v = 0.53
© 2019 Baker Hughes, a GE company, LLC. All rights reserved.