Switch Settings
The discrete output switch can be opened or closed in response to conditions that the SVI FF
detects. This action is defined via DISCRETE_SWITCH_1_CONF (Discrete Switch 1 on the SVI FF
software) and are:
NOTE
0.
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
70 |
BHGE
The directional state of the switch is set using the Software Switches
tab or using the DD's DISCRETE_SWITCH_1_CONF.DIRECTION.
Disabled - the switch is always inactive (default).
DO Block - the switch's state is linked to the state of a DO block. If the
DO block feedback configuration changes, then the switch changes
state. The DO switch auto-detects which DO block has the matching
CHANNEL and translates 0 to inactive and non-0 to active. This is
configured using the Software Switches tab on the DTM or using the
DD.
Fault State - the switch is activated whenever a fault occurs and the
switch remains activated until the SVI FF status is cleared.
Not in Normal - the switch is activated whenever the mode in not
Normal.
Maintenance Required - the switch is activated whenever the device
has an alert that requires maintenance.
Warning Data - the switch is activated whenever the TB block error
Warning Data bit is set. This is manifested as a maintenance needed
soon indication.
Air Supply Alert - the switch is activated whenever there is an air sup-
ply alert. This is configured using the Pressure Alarms tabs on the
DTM or using the DD.
Travel Deviation Alert - the switch is activated whenever a travel
deviation alert occurs. This is configured using the Travel Alarms tabs
on the DTM or using the DD.
Position HI Alert - the switch is activated whenever a user-configured
Position HI alert setting is exceeded. This is configured using the Posi-
tion Alarms tabs on the DTM or using the DD.
Position LO Alert - the switch is activated whenever a user-config-
ured Position LO alert setting is exceeded. This is configured using
the Position Alarms tabs on the DTM or using the DD.
Always Active - the switch is always active and does not change
state.