OFFLINE_DIAGNOSTIC
(68)
DIAGNOSTIC_
CONFIGURATION (69)
START_POSITION (1)
176 |
BHGE
Table 31 Transducer Block Parameters (Continued)
Initial
Mode
Range
Value
See
0
Man
Descrip-
tion
40
Any
Description
Should be used by method or DTM only.
Offline valve diagnostic procedure command and status.
Writing to this parameter triggers the procedure to exe-
cute the following procedures:
1. Execute Valve Signature: Not available for standard
diagnostics.
2. Execute Ramp Test: Not available for standard diag-
nostics.
3. Save current signature as Baseline: Not available for
standard diagnostics.
4. Save current signature as Custom: Not available for
standard diagnostics.
5. Save current signature as Current: Not available for
standard diagnostics.
6. Prepare Baseline for Upload: Not available for stan-
dard diagnostics.
7. Prepare Custom for Upload: Not available for stan-
dard diagnostics.
8. Prepare Current for Upload: Not available for stan-
dard diagnostics.
9. Execute Step Test: Not available for standard diag-
nostics.
10. Save current signature as Factory: Not available
for standard diagnostics.
99. Cancel Diagnostic.
This parameter may be written only when the parameter
DIAGNOSTIC_CONFIGURATION contains correct values of
sub-parameters. It means that DIAGNOSTIC_CONFIGURA-
TION must be written prior to OFFLINE_DIAGNOSTIC.
Reading this parameter provides the status of the last
Offline Procedure:
0.Not Running.
100. Running.
Should be used by method or DTM only.
Applicable to: All
Start position for the test. May be above or below End
position.
Range is -5 to full open +5.