GE Baker Hughes Masoneilan SVI FF Installation And Operation Manual page 188

Digital positioner
Table of Contents

Advertisement

Parameter (in bold)
Sub-parameter (Index)
IP Drive Current Alert
LO (19)
Sensor Failure Alert (20) T/F
Processor Alert (21)
Valve Control Alert (22)
Commissioning Alert
(23)
Air Supply Alert (24)
Supporting
Hardware Alert (25)
ALERT_COUNTERS (96)
Deviation Alert (1)
Position HIHI Alert (2)
Position HI Alert (3)
Position Lo Alert (4)
Position LOLO Alert (5)
Set Point Timeout Alert
(6)
Near Close Alert (7)
Travel Accumulation A
Alert (8)
Travel Accumulation B
Alert (9)
Cycle Counter A Alert
(10)
188 |
BHGE
Table 31 Transducer Block Parameters (Continued)
Initial
Mode
Range
Value
T/F
F
Any
F
Any
T/F
F
Any
T/F
F
Any
T/F
F
Any
T/F
F
Any
T/F
F
Any
0 -
0
Any
0xFFFF
0 -
0
Any
0xFFFF
0 -
0
Any
0xFFFF
0 -
0
Any
0xFFFF
0 -
0
Any
0xFFFF
0 -
0
Any
0xFFFF
0 -
0
Any
0xFFFF
0 -
0
Any
0xFFFF
0 -
0
Any
0xFFFF
0 -
0
Any
0xFFFF
Description
Provides the current state of the IP Drive Current LO alert
condition.
Provides the current state of the Sensor Failure alert con-
dition.
Provides the current state of the Processor alert condition.
Provides the current state of the Valve Control alert condi-
tion.
Provides the current state of the Commissioning alert con-
dition.
Provides the current state of the Air Supply alert condition.
Provides the current state of the Supporting Hardware
alert condition.
Alert Counters Alerts - Contains a counter for each of the
alerts reported. Counters are incremented any time an
alarm condition is reported.
How many times the Deviation alert is detected.
How many times the Position HIHI alert is detected.
How many times the Position HI alert is detected.
How many times the Position LO alert is detected.
How many times the Position LOLO alert is detected.
How many times the Set Point Timeout alert is detected.
How many times the Near Close alert is detected.
How many times the Travel Accumulation A alert is
detected.
How many times the Travel Accumulation B alert is
detected.
How many times the Cycle Counter A alert is detected.
© 2019 Baker Hughes, a GE company, LLC. All rights reserved.

Advertisement

Table of Contents
loading

Table of Contents