3. Edit Block Parameters

Control engineers need to configure the blocks for the application requirements.
A. Configure the Parameter Edit Window
1. In Fieldbus Builder select Tools->Edit block parameters menu to open the Parameter Edit
window (Figure 79).
2. Select the block in the Device List menu and the current configuration appears on the right
side window. Parameters and their values are presented by the parameter index in the
block, but the actual block index is not shown on the window.
© 2019 Baker Hughes, a GE company, LLC. All rights reserved.
This may create a problem if more than one SVI FF is connected to
CAUTION
the same segment as the first 16 characters for the Resource
block are the same in both devices, the first 16 characters in the
Transducer block are the same in both devices, etc. If more than
one SVI FF device is connected to the same segment, the block
tags must be set differently in the Fieldbus Builder.
Figure 79
Parameter Edit Window
Masoneilan SVI FF Instruction Manual