GE Baker Hughes Masoneilan SVI FF Installation And Operation Manual page 214

Digital positioner
Table of Contents

Advertisement

The window on the right side presents the Network management parameters and their
values.
3. Edit the values to match the default/recommended settings by the FOUNDATION fieldbus
in document FF-940 FS 1.5 - Communication Profile chapter 5.4 Default link settings for
communication parameters on H1_31_25kbps Physical Layer networks.
4.
Click OK to accept the settings and close the window (Figure 74).
5. Ensure that the modified values are downloaded to the controller by selecting Files ->
Download.
E. Setting the Positioner's Address
To speed up the process of device discovery, reduce the working address range. If it is an
existing application with multiple devices connected, you can find the devices and their
addresses when you click on the segment and select Device List tab (Figure 75).
214 |
BHGE
Figure 74 Network Management Parameter List
Figure 75 Device List
© 2019 Baker Hughes, a GE company, LLC. All rights reserved.