GE Baker Hughes Masoneilan SVI FF Installation And Operation Manual page 184

Digital positioner
Table of Contents

Advertisement

Parameter (in bold)
Sub-parameter (Index)
FUNCTION (2)
UI_ACCESS_CONTROL
(84)
LOCK_LEVEL (1)
PASSWORD_ENABLED
(2)
PASSWORD (3)
UI_LANGUAGE (85)
APP_MODE (86)
COMPLETE_STATUS
(87)
184 |
BHGE
Table 31 Transducer Block Parameters (Continued)
Initial
Mode
Range
Value
0-13
0
MAN
OOS
MAN/
OOS
0
MAN/
OOS
T/F
F
MAN/
OOS
MAN/
OOS
0 to 6
0 -
Man/
English
OOS
Normal,
Normal
Manual,
LO, Fail-
Safe
NA
NA
Description
Custom_2_Configuration allows you to select the virtual
switch activation condition.
0. Disabled (always inactive; default).
1. Activates the switch being controlled by the DO
block.
2. Activated when position control in fault state.
3. Activated when position control is not in normal
mode.
4. Activates so the TB reports if maintenance is
required now.
5. Activates so the TB reports if maintenance is
required soon.
6. Activated when the air supply is too low.
7. Activated when a Travel Deviation Alert occurs.
8. Activated when a Position HI Alert occurs.
9. Activated when a Position LO Alert occurs.
10. Always Active.
11. Always Inactive (same as disabled).
12. Activated when a Reset occurred.
13. Activated when a Tight Cutoff state occurs.
Controls the access and functions available to the LCD
user interface display.
0: English
1: French
2: Spanish
3: Portuguese
4: Japanese
5: Italian
6: German
Processor mode.
Full status presentation - Data is mapped to the Status
presented in the processor.