DD Host
The display mode also can be changed remotely from a DD based host. To switch the
display back to normal:
1. Open the device editor in connected mode and navigate to the Transducer block.
2. Verify that the block is in LO mode.
3. Set Target mode to Manual to avoid valve movement when the mode is switched.
4. Observe the state of the display/position control by reading 86.APP_MODE parameter – it
should have a value of Setup (Figure 109).
5. From the drop-down menu select Normal (Figure 110).
6. Write the changed value of APP_MODE parameter to the device. You can verify success by
noting that the mode in is now not LO.
258 |