Exiting Failsafe Using Ams - GE Baker Hughes Masoneilan SVI FF Installation And Operation Manual

Digital positioner
Table of Contents

Advertisement

Exiting Failsafe Using AMS

To exit Failsafe:
1. Inspect the (current) faults/status flags (Figure 40).
2. If there are:
No failsafe faults, the method change app mode works, but in most cases it is
unnecessary, and simply changing the Transducer block mode works fine.
Failsafe faults, they should be addressed (removed) first by:
a. Correcting the underlying cause.
b. Clearing the faults by:
i.) Scrolling down and pressing the button at the bottom of Figure 40.
ii.) Reviewing the screen for repeating faults.
iii.) Switch mode to Manual or Auto as required.
Failsafe faults are listed in Table on page 80.
© 2019 Baker Hughes, a GE company, LLC. All rights reserved.
Figure 40 AMS Status/Faults
Masoneilan SVI FF Instruction Manual
| 81
=