GE Baker Hughes Masoneilan SVI FF Installation And Operation Manual page 179

Digital positioner
Table of Contents

Advertisement

Parameter (in bold)
Sub-parameter (Index)
Tune Flags
Completion
CHECK_PROCESS (72)
PROCESS_ID (1)
PERCENT_COMPLETE (2)
UI_CUSTOM_
CONFIGURATION (73)
© 2019 Baker Hughes, a GE company, LLC. All rights reserved.
Table 31 Transducer Block Parameters (Continued)
Initial
Mode
Range
Value
1
0
Description
Not currently used
Writing
1: Starts the autotune process.
99: Cancels the autotune process.
0: Do not run -- an attempt to write parameter Auto-
tune with this value of this sub-parameter returns
immediately Reading.
100: Running.
0: Not Run or Success or Completion code:
31: Failed actuation.
32: Control limits protected.
33: Failed open loop tuning.
45: P gain below limit.
46: P gain adjustment above limit.
55: Bias out of range.
66: Fill time exceeded.
77: Exhaust time exceeded.
88: Parameter out of range.
The current process running.
Enumerated Process ID of the currently running process.
Zero when no process is running.
0  - No Process.
1  - Find Stops process.
4  - Autotune process.
7  - Diagnostic - signature.
8  - Step Test.
15 - Ramp Test Diagnostics.
24 - Log file to dig buffer.
25 - Diagnostic buffer to log file.
26 - Standard NVMEM objects to log file.
27 - Log file to Standard NVMEM objects.
28 - Cancel a process.
Currently not implemented. Always zero.
Configuration of the custom 1 and Custom 2 display
values.
Masoneilan SVI FF Instruction Manual
| 179
=