Digital positioner
Table of Contents

Advertisement

Parameter (in bold)
Sub-parameter (Index)
TEMPERATURE (1)
ALERT_POINT (2)
DEADBAND (3)
ALERT (4)
HISTORIC ALERT (5)
ENABLE (6)
TEMPERATURE_LO_
ALERT (63)
TEMPERATURE (1)
ALERT_POINT (2)
DEADBAND (3)
ALERT (4)
HISTORIC ALERT (5)
ENABLE (6)
© 2019 Baker Hughes, a GE company, LLC. All rights reserved.
Table 31 Transducer Block Parameters (Continued)
Initial
Mode
Range
Value
-45 to 85 85
0 - 2
2
FALSE
True -
FALSE
False
True -
TRUE
False
-45 to 85 -40
0 - 2
2
FALSE
FALSE
True -
FALSE
False
True -
TRUE
False
Description
Current TEMPERATURE value.
Not writable for Standard Diagnostics version.
TEMPERATURE Value, above which the ALERT is set to True.
Not writable for Standard Diagnostics version.
TEMPERATURE change, required to clear the ALERT, once it
was set to True.
Not writable for Standard Diagnostics version.
True if the TEMPERATURE has reached above
ALERT_POINT and have not come below
(ALERT_POINT-DEADBAND).
Not writable for Standard Diagnostics version.
True if ALERT is true.
Not changed if ALERT is false.
Not writable for Standard Diagnostics version.
True - Enables the ALERT to be reported according to the
configuration.
False - Disables ALERT reporting.
Not writable for Standard Diagnostics version.
Low temperature alert.
Not writable for Standard Diagnostics version.
Current TEMPERATURE value.
Not writable for Standard Diagnostics version.
TEMPERATURE Value, below which the ALERT is set to True.
Not writable for Standard Diagnostics version.
TEMPERATURE change, required to clear the ALERT, once it
was set to True.
Not writable for Standard Diagnostics version.
True if the TEMPERATURE has reached below ALERT_POINT
and have not come above (ALERT_POINT+DEADBAND).
Not writable for Standard Diagnostics version.
True if ALERT is true.
Not changed if ALERT is false.
Not writable for Standard Diagnostics version.
True - Enables the ALERT to be reported according to the
configuration.
False - Disables ALERT reporting.
Not writable for Standard Diagnostics version.
Masoneilan SVI FF Instruction Manual
| 173
=