Valvue; Installation Of Valvue Software, And Registration; Installation Of Cover; Display Menus - GE Baker Hughes Masoneilan SVI FF Installation And Operation Manual

Digital positioner
Table of Contents

Advertisement

ValVue

The third digital interface available for the SVI FF is Masoneilan's ValVue software. ValVue
provides a user friendly interface that facilitates set up and operation of the positioner. ValVue
is used to configure, calibrate and perform valve diagnostics.

Installation of ValVue Software, and Registration

For assistance contact the nearest sales office, your local representative or email
svisupport@ge.com.

Installation of Cover

The cover of the SVI FF is a critical component for safety in Hazardous Areas. To ensure safe
operation the flat surfaces of the cover and the housing must be clean and absolutely free of
particles or dents. The O-ring must be securely located in its groove. Install the cover and
tighten all four screws. There must be no gap between the housing and cover.

Display Menus

When you leave the NORMAL mode to go to SETUP mode the valve is placed in the last
position it was in when leaving NORMAL. When in SETUP mode the device does not respond to
the system processed setpoint. However, the SVI FF unit can still respond to commands,
including commands to position the valve. When you switch to the VIEW DATA or VIEW ERR
menus from the NORMAL operate mode menu the valve is still in NORMAL mode and still
responds to the system processed setpoint.

NORMAL Operating Mode Menus

Pressing any display key
while in Normal Cycling
moves to Normal mode
NORMAL Cycling
Menu
© 2019 Baker Hughes, a GE company, LLC. All rights reserved.
+
SETUP
NORMAL
*
BAS
SETUP
Figure 56 NORMAL Operation Menu Structure
+
+
VIEW
VIEW ERR
DATA
*
*
VIEW
VIEW
ERROR
DATA
Menu
Menu
+
+
ADV
METHOD
SETUP
+
+
SIMULATN
CLR ERR
*
*
CLR ERR
+
*
MAN POS
Masoneilan SVI FF Instruction Manual
+
| 133
=

Advertisement

Table of Contents
loading

Table of Contents