Parameter (in bold)
Sub-parameter (Index)
ENABLE (6)
POSITION_HI_ALERT
(28)
POSITION (1)
ALERT_POINT (2)
DEADBAND (3)
ALERT (4)
HISTORIC ALERT (5)
ENABLE (6)
POSITION_LO_ALERT
(29)
POSITION (1)
ALERT_POINT (2)
DEADBAND (3)
ALERT (4)
HISTORIC ALERT (5)
ENABLE (6)
POSITION_
LOLO_ALERT (30)
POSITION (1)
158 |
BHGE
Table 31 Transducer Block Parameters (Continued)
Initial
Mode
Range
Value
TRUE
TRUE
105
1
0
0
TRUE
TRUE
-51 to
-5
199
0.1-10
1
0
0
0
0
0
TRUE
Description
True - Enables the ALERT to be reported according to the
configuration.
False - Disables ALERT reporting.
Current valve position in travel units. Presented here for
convenience.
POSITION Value, above which the ALERT is set to True.
Should be set above POSITION_LO_ALERT.ALERT_POINT.
POSITION change, required to clear the ALERT, once it was
set to True.
True if the position has reached above ALERT_POINT and
have not come below (ALERT_POINT-DEADBAND).
True if ALERT is true.
Not Changed if ALERT is false.
True - Enables the ALERT to be reported according to the
configuration.
False - Disables ALERT reporting.
Current valve position in travel units. Presented here for
convenience.
POSITION Value, below which the ALERT is set to True.
Should be set below POSITION_HI_ALERT.ALERT_POINT.
POSITION change, required to clear the ALERT, once it was
set to True.
True if the position has reached below ALERT_POINT and
have not come above (ALERT_POINT+DEADBAND).
True if ALERT is true.
Not Changed if ALERT is false.
True - Enables the ALERT to be reported according to the
configuration.
False - Disables ALERT reporting.
Current valve position in travel units. Presented here for
convenience.