GE Baker Hughes Masoneilan SVI FF Installation And Operation Manual page 170

Digital positioner
Table of Contents

Advertisement

Parameter (in bold)
Sub-parameter (Index)
VALUE (2)
PRESSURE_RANGE (51)
EU_100 (1)
EU_0 (2)
UNITS_INDEX (3)
DECIMAL (4)
SUPPLY_
PRESSURE_HI_ALERT
(52)
PRESSURE (1)
ALERT_POINT (2)
DEADBAND (3)
ALERT (4)
HISTORIC ALERT (5)
ENABLE (6)
170 |
BHGE
Table 31 Transducer Block Parameters (Continued)
Initial
Mode
Range
Value
Man,
OOS
0-1034.2
1034.2
0-1034.2
0
See
kPa
Descrip-
(1133)
tion
3
3
0-1034.2
1034.2
0 - 20
0.5
FALSE
True -
FALSE
False
True -
TRUE
False
Description
No value for Standard Diagnostics version.
The range of the supply pressure.
This parameter has to be synchronized with the scale
parameter of the Analog Output block.
Upper Range for the supply pressure. The value should be
recalculated if the Unit Index is changed. This value is not
user changeable.
Lower Range for the supply pressure. This value is not user
changeable.
Engineering Units The following values should be avail-
able:
1133: kPa.
1141: psi.
1137: bar.
3
Not writable for Standard Diagnostics version.
Current SUPPLY_PRESSURE value.
Not writable for Standard Diagnostics version.
SUPPLY_PRESSURE Value, above which the ALERT is set to
True. Should be in the units of pressure.
Not writable for Standard Diagnostics version.
SUPPLY_PRESSURE change, required to clear the ALERT,
once it was set to True.
Not writable for Standard Diagnostics version.
True if the SUPPLY_PRESSURE has reached above
ALERT_POINT and have not come below
(ALERT_POINT-DEADBAND).
Not writable for Standard Diagnostics version.
True if ALERT is true.
Not changed if ALERT is false.
Not writable for Standard Diagnostics version.
True - Enables the ALERT to be reported according to the
configuration.
False - Disables ALERT reporting.
Not writable for Standard Diagnostics version.
© 2019 Baker Hughes, a GE company, LLC. All rights reserved.