GE Baker Hughes Masoneilan SVI FF Installation And Operation Manual page 174

Digital positioner
Table of Contents

Advertisement

Parameter (in bold)
Sub-parameter (Index)
IP_DRIVE_CURRENT
(64)
STATUS (1)
VALUE (2)
IP_DRIVE_
CURRENT_HI_ALERT
(65)
CURRENT (1)
ALERT_POINT (2)
DEADBAND (3)
TIME (4)
ALERT (5)
HISTORIC ALERT (6)
ENABLE (7)
IP_DRIVE_
CURRENT_LO_ALERT
(66)
CURRENT (1)
ALERT_POINT (2)
174 |
BHGE
Table 31 Transducer Block Parameters (Continued)
Initial
Mode
Range
Value
-20 to
100
120
from 0 to
5
20
1 to 60
60
FALSE
FALSE
True -
FALSE
False
True -
TRUE
False
-20 to
0
120
Description
The actual drive current to control the IP converter.
Presented in percentage.
No value for Standard Diagnostics version.
No value for Standard Diagnostics version.
Float value in % of IP Current MAX.
No value for Standard Diagnostics version.
Alarm reported, when the Drive Current through the I/P
converter is too High.
Not writable for Standard Diagnostics version.
Current IP DRIVE CURRENT value.
Not writable for Standard Diagnostics version.
When the CURRENT Value is above ALERT POINT, the
ALERT is set to True.
Not writable for Standard Diagnostics version.
Not writable for Standard Diagnostics version.
The user defined allowable duration in seconds of CUR-
RENT below ALERT_POINT before alert is set to True.
Not writable for Standard Diagnostics version.
True if the CURRENT has reached below ALERT_POINT and
have not come above ALERT_POINT.
Not writable for Standard Diagnostics version.
True if ALERT is true.
Not changed if ALERT is false.
Not writable for Standard Diagnostics version.
True - Enables the ALERT to be reported according to the
configuration.
False - Disables ALERT reporting.
Not writable for Standard Diagnostics version.
Alarm reported, when the Drive Current through the I/P
converter is too Low.
Not writable for Standard Diagnostics version.
Current IP DRIVE CURRENT value.
Not writable for Standard Diagnostics version.
When the CURRENT Value is below ALERT POINT, the
ALERT is set to True.
Not writable for Standard Diagnostics version.