GE Baker Hughes Masoneilan SVI FF Installation And Operation Manual page 153

Digital positioner
Table of Contents

Advertisement

Parameter (in bold)
Sub-parameter (Index)
UNITS_INDEX (3)
DECIMAL (4)
POSITION_LIMITS (14)
LIMITS_PROTECTED (1)
ENABLE_HI (2)
ENABLE_LO (3)
LIMIT_HI (4)
LIMIT_LO (5)
ENABLE_RATE_HI (6)
ENABLE_RATE_LO (7)
LIMIT_RATE (8)
FINAL_
VALUE_CUTOFF_HI (15)
ENABLE (1)
CUTOFF_POINT_HI (2)
FINAL_
VALUE_CUTOFF_LO
(16)
ENABLE (1)
CUTOFF_POINT_LO (2)
FINAL_
POSITION_VALUE (17)
STATUS (1)
VALUE (2)
© 2019 Baker Hughes, a GE company, LLC. All rights reserved.
Table 31 Transducer Block Parameters (Continued)
Initial
Mode
Range
Value
%(1342)
%(134
2)
2
2
Man
T/F
F
T/F
F
T/F
F
-25 to
125
+125
-25 to
-25
+125
T/F
F
T/F
F
0.5 to
100.1
100.1
T/F
F
Man
80%
98
Man
T/F
F
Man
20%
2
Man
Description
Engineering Units at 100. Fixed to %(1342).
2
Position Limits defined as percentage of valve travel.
Position Limits change is restricted. If True, ENABLE_HI and
ENABLE_LO cannot be changed. This should be set to
False before running diagnostic procedures.
Position Limit HI enabled.
Position Limit LO enabled.
Position Limit HI Point. The working setpoint is limited be
this value.
Position Limit LO Point.
Enables working setpoint Position Rate Limit when the
valve setpoint increased.
Enables working setpoint Position Rate Limit when the
valve setpoint decreased.
Position Rate Limit.
If the working position is higher than this value, the valve is
forced to its maximum high value (fully opened).
True if CUTOFF_HI algorithm to be enabled.
Cut-Off point HI. Valve is fully open to after this point. From
80% to 200%.
If the working position is less than this value, the valve is
forced to its maximum low value (fully closed).
True if CUTOFF_LO algorithm to be enabled.
Cut-Off point LO. Valve is fully closed to after this point.
Below 20% to at least -50%.
The actual valve position and status.
Actual position value.
Masoneilan SVI FF Instruction Manual