Digital positioner
Table of Contents

Advertisement

Parameter (in bold)
Sub-parameter (Index)
ACTIVATE_
CONTROL_SET (18)
ACTIVE_
CONTROL_SET (19)
Selector (1)
P (2)
I (3)
D (4)
Padj (5)
Beta (6)
PosComp (7)
DeadZone (8)
NonLin (9)
CUSTOM_
CONTROL_SET (20)
P (1)
I (2)
D (3)
154 |
BHGE
Table 31 Transducer Block Parameters (Continued)
Initial
Mode
Range
Value
0,1,2,3,4,5
0
Auto
,6,7,10,11,
255
NA
NA
NA
NA
NA
NA
NA
NA
NA
max.
Auto
5000
max.
Auto
1000
max. 200
Auto
Description
Allows copying of the Working Control Set or the Backup
Control Set to the Active control set. The following com-
mands are available:
0: Activate Custom Control Set.
1: Activate Control Set 1(Slowest).
2: Activate Control Set 2.
3: Activate Control Set 3.
4: Activate Control Set 4.
5: Activate Control Set 5(Fastest).
6: Activate Control Set 6 (Double Acting - Slow).
7: Activate Control Set 7 (Double Acting- Fast).
10: Restore Control set (make Backup Control Set
Active).
11: Make active control set as Custom control set.
255: Do Nothing.
See Table 3 on page 48 and Table 4 on page 48 for tables
recommending control sets by valve.
This read-only parameter contains the control parameters
currently used by the positioner.
Identifies the active control set.
User editable values. These values do not change the
active control set until ACTIVATE_CONTROL_SET is not set
to 0.