Parameter (in bold)
Sub-parameter (Index)
PRESSURE_EXTREMES
(115)
SUPPLY_PRESSURE_-
MAX (1)
SUPPLY_PRES-
SURE_MIN (2)
ACTUATOR_A_MAX (3)
ACTUATOR_A_MIN (4)
ACTUATOR_B_MAX (5)
ACTUATOR_B_MIN (86
PILOT_MAX (7)
PILOT_MIN (8)
TEMPERATURE_
EXTREMES (116)
TEMPERATURE_MAX (1)
TEMPERATURE_MIN (2)
IP_CURRENT_
EXTREMES (117)
IP_CURRENT_MAX (1)
IP_CURRENT_MIN (2)
© 2019 Baker Hughes, a GE company, LLC. All rights reserved.
Table 31 Transducer Block Parameters (Continued)
Initial
Mode
Range
Value
Auto,
Man,
OOS
-25 to
-25
1050
-25 to
1050
1050
-25 to
-25
1050
-25 to
1050
1050
-25 to
-25
1050
-25 to
1050
1050
-25 to
-25
1050
-25 to
1050
1050
Auto,
Man,
OOS
-40 to 85 -40
-40 to 85 85
Auto,
Man,
OOS
-25 to
-25
150
-25 to
150
150
Description
Minimum and Maximum Pressure values observed since
the last update from the user.
Note: The extremes are evaluated every 0.5 seconds.
Faster changes in the pressure may not be registered.
SUPPLY_PRESSURE: Maximum value detected since last
update from the user.
SUPPLY_PRESSURE: Minimum value detected since last
update from the user.
ACTUATOR_A: Maximum value detected since last update
from the user.
ACTUATOR_A: Minimum value detected since last update
from the user.
ACTUATOR_B: Maximum value detected since last update
from the user.
ACTUATOR_B: Minimum value detected since last update
from the user.
PILOT_PRESSURE: Maximum value detected since last
update from the user.
PILOT_PRESSURE: Minimum value detected since last
update from the user.
Minimum and Maximum Temperature values observed
since the last update from the user.
Note: The extremes are evaluated every 0.5 seconds.
Faster changes in the temperature may not be registered.
TEMPERATURE: Maximum value detected since last
update from the user.
TEMPERATURE: Minimum value detected since last update
from the user.
Minimum and Maximum IP_Current values observed since
the last update from the user.
Note: The extremes are evaluated every 0.5 seconds.
Faster changes in the IP current may not be registered.
IP_DRIVE_CURRENT: Maximum value detected since last
update from the user.
IP_DRIVE_CURRENT: Minimum value detected since last
update from the user.
Masoneilan SVI FF Instruction Manual