CHAR_SELECTION.TYPE to one of:
See "Transducer Block Parameters" on page 149. for further settings.
2. For the AO block set as below:
Step 6: Run Find Stops METHOD
Use a configuration tool (DD, SVI FF local pushbuttons or software) to run METHOD.
Step 7: Run Auto Tune METHOD
Use a configuration tool (DD, SVI FF local pushbuttons or software) to run METHOD.
When finished, ensure the Transducer block is returned to Auto.
Downloads
To download the complete user manual, DD, SVI FF Advanced DTM and the ValVue Suite trial
program, visit: https://valves.bhge.com/resource-center.
34 |
BHGE
0. Linear
3. Quick Open (reversal
from Equal Percentage
(50:1))
PV_SCALE.UNIT INDEX = %
SHED_OPT = NORMAL
SHED NORMAL RETURN
This procedure moves the valve.
WARNING
This procedure moves the valve.
WARNING
If the Transducer block is switched to Auto, it then follows the
CAUTION
setpoint received from the AO block (if scheduled).
if you fail to switch the Transducer block to Auto, then the valve
will not be in control.
1. Equal Percentage (30:1)
4. Custom
XD_SCALE.UNIT INDEX = %
© 2019 Baker Hughes, a GE company, LLC. All rights reserved.
2. Equal Percentage (50:1)
5. Camflex Percentage
CHANNEL = Position