Device DTM

To switch the device display to Normal mode from the device DTM:
1. Open the device DTM and ensure that it is in Connected state (Figure 97).
2. Set the TB to Manual mode to avoid valve movement, (1. in Figure 97.).
3. Select Positioner State from the DTM Menu (2. in Figure 97).
4. From the Hardware Group select Details . . . (3. in Figure 97.)
In Position Control State group box (at the bottom of the screen) you can see that the
device is being setup from the local display (4. in Figure 98).
5. Press Set to Normal (5. in Figure 98) to switch the display back to Normal mode and the
positioner follows the setpoint received from Transducer block. You can verify succes by
noting that the TB state is not LO, as in Figure 97
252 |
BHGE
Figure 97 SVI FF DTM
Figure 98 Position Control State
© 2019 Baker Hughes, a GE company, LLC. All rights reserved.