Use Valvue To Check Magnet Position; Step 4: Checking The Air Supply - GE SVi 1000 Masonelian Quick Start Manual

Table of Contents

Advertisement

Use ValVue to Check Magnet Position

To check the magnet using ValVue:
1. Connect to the positioner in accordance with the ValVue instructions.
a. Ensure the positioner has been installed and set up with a HART
HART
computer that is connected to the HART
b. Run ValVue.
c. Select the installed positioner from the list of Connected Devices.
d. Select the Check tab to view the current operating conditions of the selected
positioner.
2. Read Raw Position data. When the valve is:

Step 4: Checking the Air Supply

To check the air supply:
1. Turn on the air supply.
2. Adjust the filter regulator.
3. Supply pressure must be a minimum of 5 psi greater than the spring range of the
actuator but may not exceed the rated actuator pressure. Refer to the valve or
actuator instruction manual.
4. Inspect the tubing connections between the filter-regulator and the positioner for
leaks.
5. Verify that the tubing is not bent or crushed.
6. Verify that all fittings are leak tight.
CAUTION
© 2016 General Electric Company. All rights reserved
®
compliant communications loop, if required, install ValVue on the
Closed, the value should be between – 1000 and +1000 for a reciprocating
valve or a 60° rotation rotary valve.
At mid-travel, the value should be between –1000 and +1000 for a greater
than 60° rotation rotary valve.
Do not use Teflon pipe seal tape. The Teflon tape can shred into
particles that are harmful to the pneumatic components.
®
modem.
.
Masoneilan SVi1000 Positioner Quick Start Guide =| 43
®