ComAp IG-NT Reference Manual page 91

Inteli new technology modular gen-set controller, multiple internal engines application - sw configuration mint
Hide thumbs Also See for IG-NT:
Table of Contents

Advertisement

N
OTE
As there is always a connection between the N and PE wires at the mains side the
generator neutral contactors are always open when the mains breaker is closed.
Setpoint: WatchedContr
Group
Process Control
Range [units]
0 .. 16 [min]
Related FW
3.0
Description
This setpoint is used at redundant controller to specify the address of the related
main controller in
controller is not used as redundant or if
Group: Basic settings
Setpoint: Nomin Power
Group
Basic Settings
Range [units]
1 .. 32000 [kW]
Related FW
3.0
Force value
YES
possible
Description
This setpoint is used for adjusting the gen-set nominal (rated) power, i.e. the
maximum allowed gen-set power level.
IS-NT controllers provide two independent power derating functions, which can be
used for derating of the gen-set according to an analog value (e.g. temperature).
See the setpoints
The nominal power or derated nominal power is used as the basis (100%) for gen-
set power protections, as the upper limit of the requested power in the parallel-to-
mains operation, for power management and other functions.
N
OTE
The actual setpoint units and range depend on setting of the Power format in
GenConfig.
Setpoint: Nomin current
Group
Basic Settings
Range [units]
1 .. 10000 [A]
Related FW
3.0
Force value
YES
possible
Inteli NT MINT, SW Version 3.0, ©ComAp –May 2013
IGS-NT-MINT-3.0 Reference Guide.PDF
:
CAN-based rendundant
Derating1 strt
:
systems. Adjust this setpoint to 0 if the
wired rendundancy system
and
Derating2
strt.
is used.
91

Hide quick links:

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the IG-NT and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

This manual is also suitable for:

Ig-ntcIs-ntIg-eecIg-nt-bbIg-ntc-bbIs-ntc-bb ... Show all

Table of Contents

Save PDF