Binary input: GCBButton
Related FW
3.0
Description
This input is used for an external GCB button mounted on the switchboard. The
function of the input is identical as function of the GCB button on the controller
front panel.
The input is enabled only if the setpoint
EXTBUTTONS or BOTH.
Binary input: Load res 2
Related FW
3.0
Description
This input is used to activate the
is active by default. The set #2 is adjusted by setpoints:
C
AUTION
All controllers cooperating together in Power management must have the same
load reserve set selected.
N
OTE
It is possible to use virtual peripheries for distribution of the binary signal from one
physical switch connected to one controller to all other controllers over the CAN
bus.
Inteli NT MINT, SW Version 3.0, ©ComAp –May 2013
IGS-NT-MINT-3.0 Reference Guide.PDF
#LoadResStrt 2
and
#LoadResStop 2
switched to absolute mode
#%LdResStrt 2
and
#%LdResStop 2
switched to relative mode.
!
:
Local Button
is set to position
load reserve set #2
instead of the set #1, which
if the power management is
if the power management is
240