XAMPLE OF USING VIRTUAL PERIPHERIES FOR SIGNAL DISTRIBUTION
Binary input: Load res 3
Related FW
3.0
Description
This input is used to activate the
is active by default. The set #3 is adjusted by setpoints:
C
AUTION
All controllers cooperating together in Power management must have the same
load reserve set selected.
N
OTE
It is possible to use virtual peripheries for distribution of the binary signal from one
physical switch connected to one controller to all other controllers over the CAN
Inteli NT MINT, SW Version 3.0, ©ComAp –May 2013
IGS-NT-MINT-3.0 Reference Guide.PDF
#LoadResStrt 3
and
#LoadResStop 3
switched to absolute (kW-based) mode
#%LdResStrt 3
and
#%LdResStop 3
switched to relative (%Pnom-based) mode.
!
:
load reserve set #3
instead of the set #1, which
if the power management is
if the power management is