H
INT
To use Prelubrication, configure Binary output PRELUBR PUMP first.
Prelubrication is disabled in controller OFF mode or if Prelubr time is set to zero.
Binary output PRELUBR PUMP is opened when engine is running.
Prelubrication cycle starts with PrelubrPause after engine stop.
Prelubrication cycle starts immediately when controller power supply is switched on or when mode changes
from OFF to MAN or AUT or after Emergency stop was reset. An Alarmlist message "Not lubricated" is active
until this first lubrication cycle has been completed.
Engine cooling
Engine params: Cooling speed
Engine warming
Warming temp
Analog input
Service time alarm
Engine starting procedures
Engine params: Starting RPM
Engine starting procedure if Engine params: Fuel solenoid = DIESEL ENGINE with different setting of
FuelSol offset.
Inteli NT MINT, SW Version 3.0, ©ComAp –May 2013
IGS-NT-MINT-3.0 Reference Guide.PDF
Cooling time
Cooldown optim
AfterCoolTime
Engine params: Warming load
Warming temp
Max warm time
Engine protect: Service time 1
Service time 2
Service time 3
Service time 4
Prestart time
MaxCrank time
CrnkFail pause
Crank attempts
Idle time
Cooling pump
Cooling
Reduces
requested load
Warming
WrnServiceT1+2
WrnServiceT3+4
Prestart
Starting
Starter
Cranking
Fuel solenoid
Crank procedure
Stop solenoid
Idle run
Idle/Nominal
Operational
Ignition
19
Need help?