Setpoint: Warming load
Group
Engine params
Range [units]
0 .. 100 [%]
Related FW
3.0
Force value
YES
possible
Description
This setpoint is used to adjust the requested load level during warming period in
% of the
The warming period takes place after the gen-set has been synchronized to the
mains if the temperature measured at the logical analog input Warming Temp is
below the value of
load, which should be adjusted to cca 20-30% of the nominal load to allow the
engine reaching of it's operational temperature smoothly. The warming period is
finished either when the temperature reaches the warming level or if duration of
the warming period reaches
Setpoint: Warming temp
Group
Engine params
-32000 .. 32000 [°C]
Range [units]
Related FW
3.0
Force value
YES
possible
Description
This setpoint adjusts the warming temperature. The warming phase is finished
when either the water temperature at the logical analog input
reaches this level or the
N
OTE
Inteli NT MINT, SW Version 3.0, ©ComAp –May 2013
IGS-NT-MINT-3.0 Reference Guide.PDF
Nomin
power.
Warming
temp. The gen-set load is maintained at
Max warm
Max warm time
:
time.
Warming temp
elapses.
Warming